R-22 Retrofit Solutions

Retrofit Your R-22 A/C or Refrigeration System Today

Honeywell Genetron® Refrigerants offers non-ozone-depleting HFC alternatives to R-22. We have refrigerants specifically designed to retrofit any refrigeration or A/C system.

Find the Right Refrigerant for Your R-22 Retrofit

 
Genetron® 407C (R-407C)

  • Best capacity match to R-22
  • The most efficient R-22 retrofit option in the marketplace
  • A change to POE lubricant, or the addition of some POE to the system is required for proper oil return
  • Requires minimum of 20% POE for close-coupled systems
  • No TXV change required
  • GWP of 1774
  • Lower discharge temperature than R-22

Genetron® 422D (R-422D)

  • No oil change* or TXV** change in most installations
  • Satisfies customers looking for a “drop-in” option
  • Slightly less capacity and efficiency but lower discharge temperatures
  • Can be used with AB, MO, POE lubricants* when short connecting lines are used

*System designs vary and the addition of POE may be required to assure proper oil return.
**The mass flow of 422D is higher than that of R-22. An evaluation of the expansion device is recommended.

Find the Right Refrigerant to Retrofit Your R-22 System

 
Genetron Performax® LT (R-407F)

  • Best capacity match to R-22 in medium- and low-temperature applications
  • The most efficient R-22 retrofit option in the marketplace
  • Lowest GWP (1824) among R-22 replacements for commercial refrigeration
  • Requires POE
  • No TXV change or adjustments
  • Compressor manufacturer approvals
  • Lower discharge temperature than R-22

Genetron® 422D (R-422D)

  • Less capacity and efficiency but lower discharge temperatures
  • No oil change* or TXV** change in most installations
  • Satisfies customers looking for a “drop-in” option

Genetron® AZ-50 (R-507) and Genetron® 404A (R-404A)

  • Guaranteed capacity match to R-22
  • Requires POE lubricant
  • TXV change required
  • R-507 is the only HFC candidate suitable for retrofitting flooded R-22 systems

*System designs vary and the addition of POE may be required to assure proper oil return.
**The mass flow of 422D is higher than that of R-22. An evaluation of the expansion device is recommended.

Download our guidelines for detailed information about our Retrofit Solutions.

Retrofit Guidelines
Guide to Retrofitting A/C Systems from R-22 to R-422D or R-407C Download
HFC Retrofit Guidelines: R-404A and R-507 to R-407F Download
Literature
Guide to Alternative Refrigerants Download
R-22 retrofit options for A/C and refrigeration refrigerants Download
R-22 Allocation: Find the Right Refrigerant Solution Download
Genetron® 422D one-page information sheet Download
Genetron® 407C One-Page Information Sheet Download
Genetron Performax® LT One-page data sheet Download
Case Studies
Performax LT – R-22 Retrofit Case Study – Schnucks Market
Performax LT – R-22 Retrofit Case Study – Sprouts
Performax LT – R-22 Retrofit Case Study – Weaver Markets