A non-ozone depleting azeotropic mixture of R-125 and R-143a. It has been primarily designed to replace R-502 in low- and medium-temperature commercial refrigeration applications such as supermarket display cases and ice machines. For new equipment and retrofits.
Genetron® AZ-50®
General Information
Item | Specification |
---|---|
ASHRAE # | R-507A |
Class | HFC |
Refrigerant Type | Azeotrope |
Typical Lubricant | POE |
Substitutes | HCFC-22, R-502 |
Contains | HFC-125 (50%), HFC-143a (50%) |
Glide | No Glide |
Notes | Slightly higher pressures and efficiency than R-404A. Best choice for systems with flooded evaporators. EPA SNAP approved and UL Classified. |
Physical Properties
Property | Value |
---|---|
Chemical Name | Pentafluoroethane, Trifluoroethane |
Chemical Notation | CF3CHF2, CF3CH3 |
Molecular Weight | 98.9 |
Boiling Point (°C) | -46.7 |
Freezing Point (°C) | -116.7 |
Critical Temperature (°C) | 70.6 |
Critical Pressure (bar) | 37.05 |
Liquid Density (kg/m³) 0°C | 1156.3 |
Specific Heat of Liquid @ Constant Pressure @ 25°C (kJ/(kg.K)) | 1.5388 |
Specific Heat of Vapor @ Constant Pressure @ 25°C (kJ/(kg.K)) | 1.2253 |
Vapour Density (kg/m³) 25°C | 4.04 |
GWP | 3985 |
ODP | Non-ozone depleting |
ATEL/ODL (kg/m³) | 0.53 |
Practical Limit (kg/m³) | 0.53 |
AIT (°C) | ND |
Flammable range, %vol. in air (Based on ASHRAE Standard 34 with Match Ignition) | None |
ANSIASHRAE Standard 36-1992 Safety Group Classification | A1 |